| Power contactor, AC-3 9 A, 4 kW / 400 V 1 NC, 48 V AC, 50/60 Hz 3-pole, Size S00, Screw terminal Upright mounting position !!! Phased-out product !!! Successor is SIRIUS 3RT2 |
| Product brand name | SIRIUS |
| Product designation | power contactor |
| General technical data |
| Size of contactor | S00 |
| Degree of pollution | 3 |
| Protection class IP | |
| on the front | IP20 |
| of the terminal | IP20 |
| Mechanical service life (switching cycles) | |
| of contactor typical | 30 000 000 |
| of the contactor with added electronics-compatible auxiliary switch block typical | 5 000 000 |
| of the contactor with added auxiliary switch block typical | 10 000 000 |
| Reference code acc. to DIN EN 81346-2 | Q |
| Ambient conditions |
| Installation altitude at height above sea level | |
| maximum | 2 000 m |
| Ambient temperature | |
| during operation | -25 ... +60 °C |
| Main circuit |
| Number of poles for main current circuit | 3 |
| Number of NO contacts for main contacts | 3 |
| Number of NC contacts for main contacts | 0 |
| Operating current | |
| at AC-1 at 400 V | |
| — at ambient temperature 40 °C rated value | 22 A |
| at AC-1 | |
| — up to 690 V at ambient temperature 40 °C rated value | 22 A |
| — up to 690 V at ambient temperature 60 °C rated value | 20 A |
| at AC-3 | |
| — at 400 V rated value | 9 A |
| at AC-4 at 400 V rated value | 8.5 A |
| Operating current | |
| at 1 current path at DC-1 | |
| — at 24 V rated value | 20 A |
| — at 110 V rated value | 2.1 A |
| with 2 current paths in series at DC-1 | |
| — at 24 V rated value | 20 A |
| — at 110 V rated value | 12 A |
| with 3 current paths in series at DC-1 | |
| — at 24 V rated value | 20 A |
| — at 110 V rated value | 20 A |
| Operating current | |
| at 1 current path at DC-3 at DC-5 | |
| — at 24 V rated value | 20 A |
| — at 110 V rated value | 0.15 A |
| with 2 current paths in series at DC-3 at DC-5 | |
| — at 24 V rated value | 20 A |
| — at 110 V rated value | 0.35 A |
| with 3 current paths in series at DC-3 at DC-5 | |
| — at 24 V rated value | 20 A |
| — at 110 V rated value | 20 A |
| Operating power | |
| at AC-1 | |
| — at 400 V rated value | 13 kW |
| at AC-2 at 400 V rated value | 4 kW |
| at AC-3 | |
| — at 400 V rated value | 4 kW |
| — at 500 V rated value | 4.5 kW |
| — at 690 V rated value | 5.5 kW |
| Power loss [W] at AC-3 at 400 V for rated value of the operating current per conductor | 0.7 W |
| Control circuit/ Control |
| Type of voltage of the control supply voltage | AC |
| Control supply voltage at AC | |
| at 50 Hz rated value | 48 V |
| at 60 Hz rated value | 48 V |
| Control supply voltage frequency | |
| 1 rated value | 50 Hz |
| 2 rated value | 60 Hz |
| Operating range factor control supply voltage rated value of magnet coil at AC | |
| at 50 Hz | 0.8 ... 1.1 |
| at 60 Hz | 0.85 ... 1.1 |
| Apparent pick-up power of magnet coil at AC | 27 V·A |
| Inductive power factor with closing power of the coil | 0.8 |
| Apparent holding power of magnet coil at AC | 4.4 V·A |
| Inductive power factor with the holding power of the coil | 0.27 |
| Auxiliary circuit |
| Number of NC contacts for auxiliary contacts | |
| instantaneous contact | 1 |
| Number of NO contacts for auxiliary contacts | |
| instantaneous contact | 0 |
| Operating current at AC-12 maximum | 10 A |
| Operating current at AC-15 | |
| at 230 V rated value | 6 A |
| at 400 V rated value | 3 A |
| Operating current at DC-12 | |
| at 60 V rated value | 6 A |
| at 110 V rated value | 3 A |
| at 220 V rated value | 1 A |
| Operating current at DC-13 | |
| at 24 V rated value | 10 A |
| at 60 V rated value | 2 A |
| at 110 V rated value | 1 A |
| at 220 V rated value | 0.3 A |
| Contact reliability of auxiliary contacts | 1 faulty switching per 100 million (17 V, 1 mA) |
| Short-circuit protection |
| Design of the fuse link | |
| for short-circuit protection of the main circuit | |
| — with type of coordination 1 required | fuse gL/gG: 35 A |
| — with type of assignment 2 required | fuse gL/gG: 20 A |
| for short-circuit protection of the auxiliary switch required | fuse gL/gG: 10 A |
| Installation/ mounting/ dimensions |
| Mounting type | screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022 |
| Side-by-side mounting | Yes |
| Height | 57.5 mm |
| Width | 45 mm |
| Depth | 72 mm |
| Required spacing | |
| for grounded parts | |
| — at the side | 6 mm |
| Connections/Terminals |
| Type of electrical connection | |
| for main current circuit | screw-type terminals |
| for auxiliary and control current circuit | screw-type terminals |
| Type of connectable conductor cross-sections | |
| for main contacts | |
| — solid | 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²) |
| — single or multi-stranded | 2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²) |
| — finely stranded with core end processing | 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²) |
| at AWG conductors for main contacts | 2x (20 ... 16), 2x (18 ... 14), 1x 12 |
| Type of connectable conductor cross-sections | |
| for auxiliary contacts | |
| — solid | 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²) |
| — finely stranded with core end processing | 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²) |
| at AWG conductors for auxiliary contacts | 2x (20 ... 16), 2x (18 ... 14), 1x 12 |