| Capacitor contactor, AC-6b 12.5 kVAr, / 400 V 2 NC, 230 V AC, 50/60 Hz 3-pole, Size S00 screw terminal |
| Product brand name | SIRIUS |
| Product designation | capacitor contactors |
| Product type designation | 3RT26 |
| General technical data |
| Size of contactor | S00 |
| Product extension | |
| Auxiliary switch | No |
| Surge voltage resistance | |
| of main circuit rated value | 6 kV |
| of auxiliary circuit rated value | 6 kV |
| maximum permissible voltage for safe isolation | |
| between coil and main contacts acc. to EN 60947-1 | 400 V |
| Protection class IP | |
| on the front | IP20 |
| of the terminal | IP20 |
| Shock resistance at rectangular impulse | |
| at AC | 6,7g / 5 ms, 4,2g / 10 ms |
| Shock resistance with sine pulse | |
| at AC | 10,5g / 5 ms, 6,6g / 10 ms |
| Mechanical service life (switching cycles) | |
| of the contactor with added auxiliary switch block typical | 3 000 000 |
| Electrical endurance (switching cycles) | 300 000 |
| Reference code acc. to DIN EN 81346-2 | Q |
| Ambient conditions |
| Installation altitude at height above sea level | |
| maximum | 2 000 m |
| Ambient temperature | |
| during operation | -25 ... +60 °C |
| during storage | -55 ... +80 °C |
| Main circuit |
| Number of NO contacts for main contacts | 3 |
| Number of NC contacts for main contacts | 0 |
| Operating current | |
| at AC-6b at 690 V at ambient temperature 60 °C rated value | 18 A |
| Operational reactive power at AC-6b | |
| at 230 V at 50/60 Hz at ambient temperature 60 °C rated value | 0 ... 7.2 kvar |
| at 400 V at 50/60 Hz at ambient temperature 60 °C rated value | 0 ... 12.5 kvar |
| at 500 V at 50/60 Hz at ambient temperature 60 °C rated value | 0 ... 15 kvar |
| at 690 V at 50/60 Hz at ambient temperature 60 °C rated value | 0 ... 21 kvar |
| No-load switching frequency | |
| at AC | 500 1/h |
| Operating frequency at AC-6b | |
| at 230 V maximum | 180 1/h |
| at 240 V maximum | 180 1/h |
| at 400 V maximum | 180 1/h |
| at 480 V maximum | 180 1/h |
| at 500 V maximum | 180 1/h |
| at 600 V maximum | 180 1/h |
| at 690 V maximum | 180 1/h |
| Control circuit/ Control |
| Type of voltage | AC |
| Type of voltage of the control supply voltage | AC |
| Control supply voltage at AC | |
| at 50 Hz rated value | 230 V |
| at 60 Hz rated value | 230 V |
| Control supply voltage frequency | |
| 1 rated value | 50 Hz |
| 2 rated value | 60 Hz |
| Operating range factor control supply voltage rated value of magnet coil at AC | |
| at 50 Hz | 0.8 ... 1.1 |
| at 60 Hz | 0.85 ... 1.1 |
| Apparent pick-up power of magnet coil at AC | 49 V·A |
| Inductive power factor with closing power of the coil | 0.8 |
| Apparent holding power of magnet coil at AC | 7.8 V·A |
| Inductive power factor with the holding power of the coil | 0.25 |
| Closing delay | |
| at AC | 8 ... 33 ms |
| Arcing time | 10 ... 15 ms |
| Residual current of the electronics for control with signal <0> | |
| at AC at 230 V maximum permissible | 3 mA |
| Auxiliary circuit |
| Number of NC contacts for auxiliary contacts | 2 |
| attachable | 0 |
| instantaneous contact | 2 |
| Number of NO contacts for auxiliary contacts | 0 |
| attachable | 0 |
| instantaneous contact | 0 |
| Operating current of auxiliary contacts at AC-12 maximum | 10 A |
| Operating current of auxiliary contacts at AC-15 | |
| at 230 V | 6 A |
| at 400 V | 3 A |
| Operating current of auxiliary contacts at DC-13 | |
| at 24 V | 6 A |
| at 60 V | 2 A |
| at 110 V | 1 A |
| at 125 V | 0.9 A |
| at 220 V | 0.3 A |
| Contact reliability of auxiliary contacts | 0.00000001 |
| UL/CSA ratings |
| Contact rating of auxiliary contacts according to UL | A600 / Q600 |
| Short-circuit protection |
| Design of the fuse link | |
| for short-circuit protection of the main circuit | |
| — with type of coordination 1 required | gG: 40 A (690 V, 50 kA) |
| for short-circuit protection of the auxiliary switch required | gG: 10 A (500 V, 1 kA) |
| Installation/ mounting/ dimensions |
| Mounting position | +/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface |
| Mounting type | screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022 |
| Height | 125 mm |
| Width | 45 mm |
| Depth | 120 mm |
| Required spacing | |
| with side-by-side mounting | |
| — at the side | 10 mm |
| for grounded parts | |
| — at the side | 10 mm |
| Connections/Terminals |
| Type of electrical connection | |
| for main current circuit | screw-type terminals |
| for auxiliary and control current circuit | screw-type terminals |
| Type of connectable conductor cross-sections | |
| for main contacts | |
| — solid | 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm² |
| — stranded | 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm² |
| — single or multi-stranded | 2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), 2x 4 mm² |
| — finely stranded with core end processing | 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²) |
| at AWG conductors for main contacts | 2x (20 ... 16), 2x (18 ... 14), 2x 12 |
| Type of connectable conductor cross-sections | |
| for auxiliary contacts | |
| — solid | 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm² |
| — single or multi-stranded | 2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), 2x 4 mm² |
| — finely stranded with core end processing | 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²) |
| at AWG conductors for auxiliary contacts | 2x (20 ... 16), 2x (18 ... 14), 2x 12 |
| Type of minimum connectable cross-section for main contacts at AC-6b | |
| at 40 °C | 1x 4 mm², 2x 2.5 mm² |
| at 60 °C | 2x 4 mm² |
| AWG number as coded connectable conductor cross section for main contacts | 20 ... 12 |
| Safety related data |
| Product function | |
| Mirror contact acc. to IEC 60947-4-1 | No |
| positively driven operation acc. to IEC 60947-5-1 | No |
| Protection against electrical shock | finger-safe |