3VA1063-2ED36-0AA0
MCCB_IEC_FS100_63A_3P_16KA_TM_ FTFM

From SIEMENS

circuit breaker 3VA1 IEC frame 100 breaking capacity class B Icu=16kA @ 415V 3-pole, line protection TM210, FTFM, In=63A overload protection Ir=63A fixed short-circuit protection Ii=10 x In clamp connection
Model
Product brand nameSENTRON
Product designationMolded case circuit breaker
Product versionLine protection
Design of the overcurrent releaseTM210
Protective function of the overcurrent releaseLI
Number of poles3
General technical data
Rated insulation voltage Ui800 V
Max. rated operational voltage Ue with AC 50/60Hz690 V
Max. rated operational voltage Ue with DC500 V
Power loss [W] / maximum17.3 W
Active power loss / for rated value of the current / at AC / in hot operating state / per pole5.77 W
Latching - endurance15 000
Electrical endurance (switching cycles) / at AC-1 / at 380/415 V 50/60 Hz8 000
Electrical endurance (switching cycles) / at AC-1 / at 690 V 50/60 Hz8 000
Neutral conductors / upgradeable/retrofittableNo
Ground fault monitoring versionWithout
Product function
communication functionNo
other measurement functionNo
Net weight1.009 kg
Electricity
Max. rated operational voltage of the size of the circuit-breaker100 A
Rated continuous current Iu63 A
Operating current
at 40 °C63 A
at 45 °C63 A
at 50 °C63 A
at 55 °C62 A
at 60 °C61 A
at 65 °C60 A
at 70 °C58 A
Switching capacity according to IEC 60947
Switching capacity class of the circuit breakerB
Maximum short-circuit current breaking capacity (Icu)
at 240 V25 kA
at 415 V16 kA
at 440 V8 kA
at 500 V5 kA
at 690 V5 kA
Operational short-circuit current breaking capacity (Ics)
at 240 V25 kA
at 415 V16 kA
at 440 V8 kA
at 500 V5 kA
at 690 V5 kA
Short-circuit current making capacity (Icm)
at 240 V53 kA
at 415 V32 kA
at 440 V13.6 kA
at 500 V7.5 kA
at 690 V7.5 kA
Adjustable parameters
Adjustable response value current / lr min.63 A
Adjustable response value current / Ir max.63 A
Short-term delayed / tripping switchable / I2t=ON/OFFNo
Adjustable response value current / li min.630 A
Adjustable response value current / li max.630 A
Ground fault protection / tripping switchable / I2t=ON/OFFNo
Mechanical Design
Height [in]5.1 in
Height130 mm
Width [in]3 in
Width76.2 mm
Depth [in]2.8 in
Depth70 mm
Connections
Arrangement of electrical connectors / for main current circuitFront terminal
Type of electrical connection / for main current circuitbox terminal
Type of connectable conductor cross-section, round conductor terminal, stranded1 x (1.5 - 70 mm²)
Auxiliary circuit
Number of CO contacts / for auxiliary contacts0
Accessories
Product extension / optional / motor driveNo
Environmental conditions
Protection class IP / on the frontIP40
Ambient temperature
during operation / minimum-25 °C
during operation / maximum70 °C
during storage / minimum-40 °C
during storage / maximum80 °C

External links