BVP:077630 LDC8625-K-3,2-3ADU
From SIEMENS
| LDC8625-K-3.2-3ADU Standard length 3.2 m with 3 outgoing feeders at both ends | ||
| Model | ||
| Product designation | trunking unit for LD busbar trunking system | |
| Product type designation | LDC8625-K-3,2-3ADU | |
| General technical data | ||
| Configuration of the busbars | L1,L2,L3,N,N,L3,L2,L1,PE | |
| Voltage | ||
| Insulation voltage | ||
| at AC / rated value | 1 000 V | |
| at DC / rated value | 1 200 V | |
| Protection class | ||
| Protection class IP | IP54 | |
| Electricity | ||
| Number of circuits / in a trunking unit | 1 | |
| Short-time current resistance (Icw) / at 690 V | ||
| limited to 0.1 s / rated value | 130 kA | |
| limited to 1 s / rated value | 116 kA | |
| Surge current resistance / at 690 V / rated value | 286 kA | |
| Main circuit | ||
| Operating frequency / rated value | ||
| minimum | 16.7 Hz | |
| maximum | 60 Hz | |
| Operating voltage / at AC | ||
| at 50 Hz / rated value / maximum | 1 000 V | |
| at 60 Hz / rated value / maximum | 1 000 V | |
| Operating current | ||
| for circuit 1 / at AC / at 50 Hz / for horizontal busbar box with flat busbars / rated value / maximum | 3 000 A | |
| for circuit 1 / at AC / at 50 Hz / for vertical busbar box / rated value | 3 600 A | |
| for circuit 1 / at AC / at 50 Hz / rated value / maximum | 3 600 A | |
| for circuit 1 / at AC / at 60 Hz / rated value / maximum | 3 600 A | |
| Appearance | ||
| Color | light grey | |
| Product details | ||
| Product component / Fire shielding | No | |
| Number | ||
| Number of conductors | 9 | |
| Connections | ||
| Conductor cross section / of the (PE)N | 2 464 mm² | |
| Tap-off points | ||
| Arrangement of the outgoing points | single-sided | |
| Outgoing point distance | 1 m | |
| Number of outgoing points / maximum | 3 | |
| Mechanical Design | ||
| Height | 180 mm | |
| Width | 240 mm | |
| Mounting position / of the busbar trunking unit | horizontal | |
| Length | 3 200 mm | |
| Length | ||
| of the busbar trunking unit | 3.2 m | |
| Mounting type | ceiling / wall | |
| Material / of the busbar | copper | |