BVP:213633 LXC0551-3-1AD
From SIEMENS
| LXC0551-3-1AD STR.TRUNK. WITH 1 TAP-OFF | ||
| Model | ||
| Product designation | trunking unit for LX busbar trunking system | |
| Product type designation | LXC0551-3-1AD | |
| General technical data | ||
| Configuration of the busbars | L1,L2,L3,N,PE | |
| Voltage | ||
| Insulation voltage | ||
| at AC / rated value | 690 V | |
| at DC / rated value | 800 V | |
| Protection class | ||
| Protection class IP | IP54 | |
| Electricity | ||
| Number of circuits / in a trunking unit | 1 | |
| Short-time current resistance (Icw) / at 1000 V / limited to 1 s / rated value | 75 kA | |
| Surge current resistance / at 1000 V / rated value | 165 kA | |
| Main circuit | ||
| Operating frequency / rated value | ||
| minimum | 50 Hz | |
| maximum | 50 Hz | |
| Operating voltage / at AC | ||
| at 50 Hz / rated value / maximum | 690 V | |
| Operating current | ||
| for circuit 1 / at AC / at 50 Hz / rated value / maximum | 2 000 A | |
| for circuit 2 / at AC / at 50 Hz / rated value / maximum | 2 000 A | |
| Appearance | ||
| Color | light grey | |
| Product details | ||
| Product component / Fire shielding | No | |
| Number | ||
| Number of conductors | 4 | |
| Number of conductors / without PE | 4 | |
| Connections | ||
| Conductor cross section / of the (PE)N | 712 mm² | |
| Tap-off points | ||
| Arrangement of the outgoing points | single-sided | |
| Number of outgoing points / maximum | 1 | |
| Mechanical Design | ||
| Height | 207 mm | |
| Width | 145 mm | |
| Mounting position / of the busbar trunking unit | horizontal / vertical | |
| Length | 3 000 mm | |
| Length | ||
| of the busbar trunking unit | 3 m | |
| Mounting type | ceiling / wall | |
| Material / of the busbar | copper | |