Product Datasheet Search Results:

3EJ3036-0CH51-4.pdf2 Pages, 2792 KB, Original
3EJ3036-0CH51-4
Siemens
SURGE ARRESTER 3EJ3

Product Details Search Results:

Digitheadinc.com/100C23EJ300
767 Bytes - 02:03:44, 15 January 2026
Mtronpti.com/M12533EJ30.000000MHZ
{"Status":"ACTIVE","Lead Free":"Yes","Terminal Finish":"NOT SPECIFIED","Mounting Feature":"SURFACE MOUNT","Mfr Package Description":"ROHS COMPLIANT, ULTRA MINIATURE, CERAMIC, LEADLESS PACKAGE-4","Operating Temperature-Min":"-10 Cel","Load Capacitance":"18 pF","Physical Dimension":"L3.2XB2.5XH0.8 (mm)/L0.126XB0.098XH0.031 (inch)","Crystal/Resonator Type":"PARALLEL - FUNDAMENTAL","Operating Frequency-Nom":"30 MHz","Operating Temperature-Max":"60 Cel","Series Resistance":"50 ohm","Drive Level":"10 uW","Manufac...
1313 Bytes - 02:03:44, 15 January 2026
Siemens.com/3EJ3002-0CB51-4
SURGE ARRESTER 3EJ3 FOR MEDIUM VOLTAGE SYSTEMS FOR OUTDOOR USE APPLIED STANDARD: IEC60099-4 UR=2.0KV, UC=1.6KV NOMINAL DISCHARGE CURRENT 20KA URES (10KA, 8/20) = 4.5KV CHARGE TRANSFER RATING 3.6C THERMAL ENERGY RATING 14KJ/KV SHORT-CIRCUIT CURRENT 65KA CREEPAGE DISTANCE 390MM HEIGHT 172MM CARDBOARD PACKAGING Electrical data Standard IEC 60099-4 Designation / of arrester class SH Discharge current / according to IEC 60099-4 / rated value 20.0\u00a0kA Discharge capacity of electrical charge 3.6\u00a0C Voltage...
5082 Bytes - 02:03:44, 15 January 2026
Siemens.com/3EJ3003-0CB51-4
SURGE ARRESTER 3EJ3 FOR MEDIUM VOLTAGE SYSTEMS FOR OUTDOOR USE APPLIED STANDARD: IEC60099-4 UR=3.0KV, UC=2.4KV NOMINAL DISCHARGE CURRENT 20KA URES (10KA, 8/20) = 6.8KV CHARGE TRANSFER RATING 3.6C THERMAL ENERGY RATING 14KJ/KV SHORT-CIRCUIT CURRENT 65KA CREEPAGE DISTANCE 390MM HEIGHT 172MM CARDBOARD PACKAGING Electrical data Standard IEC 60099-4 Designation / of arrester class SH Discharge current / according to IEC 60099-4 / rated value 20.0\u00a0kA Discharge capacity of electrical charge 3.6\u00a0C Voltage...
5084 Bytes - 02:03:44, 15 January 2026
Siemens.com/3EJ3004-0CB51-4
SURGE ARRESTER 3EJ3 FOR MEDIUM VOLTAGE SYSTEMS FOR OUTDOOR USE APPLIED STANDARD: IEC60099-4 UR=4.0KV, UC=3.2KV NOMINAL DISCHARGE CURRENT 20KA URES (10KA, 8/20) = 9.0KV CHARGE TRANSFER RATING 3.6C THERMAL ENERGY RATING 14KJ/KV SHORT-CIRCUIT CURRENT 65KA CREEPAGE DISTANCE 390MM HEIGHT 172MM CARDBOARD PACKAGING Electrical data Standard IEC 60099-4 Designation / of arrester class SH Discharge current / according to IEC 60099-4 / rated value 20.0\u00a0kA Discharge capacity of electrical charge 3.6\u00a0C Voltage...
5084 Bytes - 02:03:44, 15 January 2026
Siemens.com/3EJ3006-0AC51-4
SURGE ARRESTER 3EJ3 FOR MEDIUM VOLTAGE SYSTEMS FOR OUTDOOR USE APPLIED STANDARD: IEEE C62.11 DCV=6.0KV, MCOV=5.10KV CLASSIFYING CURRENT 20KA URES (10KA, 8/20) = 13.5KV SINGLE IMP. WITH. RATING 3.6C SWITCHING SURGE ENERGY RATING 18KJ/KV ENERGY CLASS J SHORT-CIRCUIT CURRENT 65KA LEAKAGE DISTANCE 22INCH HEIGHT 8INCH CARDBOARD PACKAGING Electrical data Standard IEEE C62.11 Energy class / according to IEEE C62.11 J Discharge current / according to IEC 60099-4 / rated value 15.0\u00a0kA Discharge capacity of elec...
5468 Bytes - 02:03:44, 15 January 2026
Siemens.com/3EJ3012-0CD51-4
SURGE ARRESTER 3EJ3 FOR MEDIUM VOLTAGE SYSTEMS FOR OUTDOOR USE APPLIED STANDARD: IEC60099-4 UR=12KV, UC=9.6KV NOMINAL DISCHARGE CURRENT 20KA URES (10KA, 8/20) = 27.0KV CHARGE TRANSFER RATING 3.6C THERMAL ENERGY RATING 14KJ/KV SHORT-CIRCUIT CURRENT 65KA CREEPAGE DISTANCE 700MM HEIGHT 244MM CARDBOARD PACKAGING Electrical data Standard IEC 60099-4 Designation / of arrester class SH Discharge current / according to IEC 60099-4 / rated value 20.0\u00a0kA Discharge capacity of electrical charge 3.6\u00a0C Voltage...
5137 Bytes - 02:03:44, 15 January 2026
Siemens.com/3EJ3045-0CJ41-4
SURGE ARRESTER 3EJ3 FOR MEDIUM VOLTAGE SYSTEMS FOR OUTDOOR USE APPLIED STANDARD: IEC60099-4 UR=45KV, UC=36.0KV NOMINAL DISCHARGE CURRENT 20KA URES (10KA, 8/20) = 101KV CHARGE TRANSFER RATING 2.8C THERMAL ENERGY RATING 10KJ/KV SHORT-CIRCUIT CURRENT 65KA CREEPAGE DISTANCE 1480MM HEIGHT 425MM CARDBOARD PACKAGING Electrical data Standard IEC 60099-4 Designation / of arrester class SH Discharge current / according to IEC 60099-4 / rated value 20.0\u00a0kA Discharge capacity of electrical charge 2.8\u00a0C Voltag...
5149 Bytes - 02:03:44, 15 January 2026
Siemens.com/3EJ3045-0CJ51-4
SURGE ARRESTER 3EJ3 FOR MEDIUM VOLTAGE SYSTEMS FOR OUTDOOR USE APPLIED STANDARD: IEC60099-4 UR=45KV, UC=36.0KV NOMINAL DISCHARGE CURRENT 20KA URES (10KA, 8/20) = 101KV CHARGE TRANSFER RATING 3.6C THERMAL ENERGY RATING 14KJ/KV SHORT-CIRCUIT CURRENT 65KA CREEPAGE DISTANCE 1480MM HEIGHT 425MM CARDBOARD PACKAGING Electrical data Standard IEC 60099-4 Designation / of arrester class SH Discharge current / according to IEC 60099-4 / rated value 20.0\u00a0kA Discharge capacity of electrical charge 3.6\u00a0C Voltag...
5149 Bytes - 02:03:44, 15 January 2026
Siemens.com/3EJ3051-0CK41-4
SURGE ARRESTER 3EJ3 FOR MEDIUM VOLTAGE SYSTEMS FOR OUTDOOR USE APPLIED STANDARD: IEC60099-4 UR=51KV, UC=40.8KV NOMINAL DISCHARGE CURRENT 20KA URES (10KA, 8/20) = 115KV CHARGE TRANSFER RATING 2.8C THERMAL ENERGY RATING 10KJ/KV SHORT-CIRCUIT CURRENT 65KA CREEPAGE DISTANCE 1640MM HEIGHT 462MM CARDBOARD PACKAGING Electrical data Standard IEC 60099-4 Designation / of arrester class SH Discharge current / according to IEC 60099-4 / rated value 20.0\u00a0kA Discharge capacity of electrical charge 2.8\u00a0C Voltag...
5152 Bytes - 02:03:44, 15 January 2026

Documentation and Support

Use our online request for specific proposed solutions or send your technical question directly to a product specialist at request:

File NameFile Size (MB)DocumentMOQSupport
3EJ3036-0CH51-4.pdf2.751Request
3EJ3036-0CH51-4.pdf2.751Request